How it works: HVAC
How a heat pump defrost cycle works
Why the outdoor unit frosts over, how it decides to melt the frost, and why it steams and goes quiet for a few minutes

Steam off the heat pump on a raw winter morning means the machine is minding itself. We would rather see that cloud a few times a day than a coil that has quietly turned into a block of ice, because the cloud is the defrost cycle doing its work.
Why the outdoor coil frosts
In winter a heat pump runs its refrigerant loop backwards, as how a central air conditioner and a heat pump move heat describes: the outdoor coil becomes the cold side and collects heat from the outside air. To take heat from cold air, the coil has to run colder than the air. Trane compares it to a glass of ice water: because the coil is colder, it collects condensation, and when the outdoor temperature is low enough the condensation freezes. Bryant’s owner manual says moisture may begin to freeze on the coil once it is below 45 F outdoors.
The busiest weather for it is not the coldest. Trane says defrost is more common when the temperature is in the 20s or 30s, and a review of defrost research from Oak Ridge National Laboratory says frost forms and builds on the outdoor coil when the air is about minus 7 to 5 C (about 19 to 41 F) and the relative humidity is above 65 percent. Frost on the fins blocks the air the outdoor fan pulls through the coil. White-Rodgers describes its defrost control as one that detects the “degradation of system performance due to ice build-up on the outdoor coil.”
How the unit decides it is time
There are two kinds of control, and the installer’s manual for your model says which one you have.
Time and temperature. The board counts compressor run time, but only while a sensor on the outdoor coil reads cold. Goodman’s manual: the timing starts when the sensor closes, at approximately 34 F (plus or minus 5), and the interval is 30, 60 or 90 minutes, picked with a jumper on the board. Carrier’s two-stage heat pump board ships set at 90 minutes and can be changed to 30, 60 or 120; it defrosts only with the outdoor air below 50 F, after the set time, and with the coil below 32 F (plus or minus 2). Carrier says the interval is field selected for local geographic requirements. Even a timed board waits for a cold coil sensor; it just cannot tell how much frost is actually there.
Demand defrost. A demand control reads two temperatures, the outdoor air and the outdoor coil, and watches the gap between them. A clean coil runs a steady number of degrees below the air. As frost chokes the airflow the coil runs colder still and the gap widens. American Standard’s installer manual describes a control that measures the gap on a clean coil and allows defrost once the gap reaches its initiate value, which is about twice the clean-coil number plus a correction. Rheem’s demand control also wants the coil below 35 F and at least 34 minutes of compressor run with the coil that cold. Trane sums up the reason for all of it: the unit only defrosts when necessary.
The few minutes of defrost
Goodman’s manual lists the moves in order: the control shifts the reversing valve to cooling mode, stops the outdoor fan and brings on supplemental heat, and the indoor blower keeps running.
- The loop runs as an air conditioner. In reverse-cycle defrost, ORNL explains, the outdoor coil acts as a condenser and the indoor coil as an evaporator: hot gas from the compressor goes into the outdoor coil and melts the frost off it from the inside.
- The outdoor fan stops in Goodman’s sequence (Trane says it may stop) while the coil heats. Bryant’s owner manual says it is normal to see steam or fog rising from the outdoor unit during defrost.
- The backup heat comes on indoors. The indoor coil is the cold side for those minutes. Carrier says the auxiliary heat assists during the defrost cycle to keep cold air from blowing out of your vents, and Amana says the auxiliary heat strips come on automatically. Trane notes that the electric heat strips are what keep the house warm during defrost.
- The sounds. Bryant says you may hear a “whoosh” at the beginning and end of the cycle, and Trane describes a swooshing as the refrigerant reverses course. Some boards soften it: Rheem’s demand control shuts the compressor off for 30 seconds at the start and end of defrost to cut the compressor noise caused by rapidly changing system pressures when the reversing valve switches.
How it knows to stop
Defrost ends when the coil sensor warms past a set point, which tells the board the ice is gone. The set point is the maker’s, and it varies:
- Goodman package heat pump: ends at about 60 F; longest defrost 12 minutes.
- Carrier two-stage heat pump: ends at 65 F (plus or minus 5).
- Lennox HP26: ends at 70 F on the liquid line; longest defrost 14 minutes.
- Rheem demand control: ends at 70 F as shipped, with 50, 60 or 80 F selectable; longest defrost 14 minutes.
- Trane 4TWX6: ends at 47 F as shipped, or 70 F with a jumper cut.
- American Standard demand control: ends on coil temperature, with a 15 minute override listed in its forced-defrost test notes.
- ICM300 replacement timer and a Bryant packaged unit: a 10 minute limit.
The time limit is the backstop: Rheem’s control, for one, keeps defrosting until the coil reaches its termination temperature or fourteen minutes have passed, whichever comes first. A normal cycle is short: Goodman says 2 to 3 minutes, and Trane says its demand-defrost cycles usually run 3 to 5. On Carrier’s board the outdoor fan waits 20 seconds after defrost ends before it starts again.
The tell worth knowing is length. Goodman writes that a defrost normally takes only 2 to 3 minutes “unless system is low on charge or outdoor conditions are severe (windy and cold),” and Trane says to call a dealer when defrost cycles last longer and longer while frost and ice start to cover the unit, or when the heat pump seems to be switching into defrost constantly.
Where the meltwater goes
Every defrost turns frost into water, and the water has to leave the unit before it freezes again. Goodman says heat pump bases have holes under the outdoor coil to drain defrost water, and that the unit must be placed so defrost water and ice drain freely. Trane’s installer guide has the unit raised 3 to 12 inches above the pad or roof, depending on local weather, so melted snow and ice drain before refreezing, and asks for the drain holes in the base pan to be kept clear. Lennox wants the base above the depth of average snows and the unit kept out from under overhanging roof lines that drop water or ice on the coil. NEEP’s cold-climate installation guide, hosted by the U.S. Department of Energy, says not to set the unit under a roof drip line without a working gutter or a drip cap or shield, and to keep it away from walkways, where refreezing meltwater can be a slip-and-fall hazard.
That is the failure the installation rules are written against: water that cannot get away, from the base pan below or the eave above, freezing onto a coil that only defrosts for a few minutes at a time.
Homeowner or technician
Leave the cycle alone. Amana says you do not need to switch on the auxiliary or emergency heat yourself in cold weather, and not to cover the heat pump in winter. Lennox’s list for snowy weather is homeowner work: clear snow away from the unit after storms without piling it against the sides, keep gutters and downspouts from draining onto or near it, and never chip at the ice, which can damage the coil, fins and fan blades, or pour hot water on the unit, since the sudden temperature change can crack components. Bryant says not to try to remove ice from the unit grille. Emergency heat is a different switch: Carrier says it shuts the heat pump off entirely and runs only the backup heat, and to use it only if the heat pump has broken down; Lennox calls it the supplemental heat running by itself.
Call a technician when the ice wins. Amana says a heavy coating of ice may mean the heat pump needs servicing, and Lennox says to call if the ice does not melt within 6 to 8 hours or refreezes quickly. The defrost interval and termination settings on the board are installer settings, and a defrost that keeps getting longer can point to low refrigerant charge, which is not homeowner work: the EPA requires technicians who service equipment that could release refrigerant to be Section 608 certified.
Related
- How a central air conditioner and a heat pump move heat covers the refrigerant loop, the reversing valve and HSPF2.
- How thermostat wiring works covers the wires that call for heat and backup heat.
- Glossary: defrost cycle, auxiliary heat, reversing valve, heat pump, compressor, refrigerant
References
- What Is the Heat Pump Defrost Cycle?. Trane. https://www.trane.com/residential/en/resources/blog/what-is-heat-pump-defrost-cycle/
- Evolution 15 SEER Single-Packaged Heat Pump Owner's Information Manual (OM607D-01). Bryant. https://www.shareddocs.com/hvac/docs/1009/Public/04/OM607D-01.pdf
- A Critical Literature Review of Defrost Technologies for Heat Pumps and Refrigeration Systems (ORNL/TM-2018/1007). Oak Ridge National Laboratory. https://info.ornl.gov/sites/publications/Files/Pub117976.pdf
- 47D40-801 Demand Defrost Control Installation Instructions. White-Rodgers (Emerson). https://climate.emerson.com/documents/non-deluxe-defrost-control-47d40-801-instructions-en-us-1569850.pdf
- Installation Instructions, GPC/GPH Package Air Conditioners and Heat Pumps (IO-398). Goodman. https://res.cloudinary.com/wholesale-plumbing/image/upload/Documents2/Goodman_GPH1460H41_Instruction_Installation_Manual.pdf
- Wiring Diagram, Performance Series 2-Stage Heat Pump 25HPA6. Carrier. https://www.shareddocs.com/hvac/docs/1009/Public/05/25HPA6-2W.pdf
- 4A7V8 Heat Pump Installer's Manual, demand defrost section. American Standard (via ManualsLib). https://manualslib.com/manual/1195238/American-Standard-4a7v8060a1000a.html?page=26
- RP13 Heat Pump Installation Instructions, demand defrost section. Rheem (via ManualsLib). https://www.manualslib.com/manual/2667719/Rheem-Rp13.html?page=35
- What Is Auxiliary Heat?. Carrier. https://www.carrier.com/us/en/residential/hvac-resources/what-is-auxiliary-heat/
- Top 10 Questions about Heat Pumps. Amana. https://www.amana-hac.com/resources/hvac-learning-center/operation/top-10-questions-about-heat-pumps
- 288BNV Evolution V Heat Pump Owner's Manual (OM288B-03). Bryant. https://econtent.adhq.com/dam/Original/700/Bryant_288BNV013000_User_Manual.pdf
- HP26 Series Heat Pump Units Installation Instructions. Lennox. https://www.lennox.com/lib/legacy-res/pdfs/installation_maintenance/lennox_hp26_iom.pdf
- Heat Pumps Installer's Guide 4TWX6 (18-AC105D1-1F-EN). Trane. https://elibrary.tranetechnologies.com/public/residential-hvac/Literature/Installation/18-AC105D1-1F-EN_04082020.pdf
- ICM300 Defrost Timer Installation Instructions. ICM Controls. https://orders.sidharvey.com/documents/ICM300C_Install.pdf
- Guide to Installing Air-Source Heat Pumps in Cold Climates. Northeast Energy Efficiency Partnerships (NEEP), hosted by the U.S. Department of Energy. https://bsesc.energy.gov/sites/default/files/2024-10/Guide%20To%20Installing%20Air-Source%20Heat.pdf
- What to Do If Your Heat Pump Is Frozen?. Lennox. https://www.lennox.com/residential/lennox-life/consumer/heat-pump-frozen
- What is the difference between Emergency Heat and Auxiliary Heat?. Lennox. https://www.lennox.com/residential/support/faqs/what-is-the-difference-between-emergency-heat-and-auxiliary-heat
- Section 608 Technician Certification Requirements. U.S. Environmental Protection Agency. https://www.epa.gov/section608/section-608-technician-certification-requirements
Every fact and number on this page comes from one of the sources above, read during the writing of this page. Codes and standards vary by jurisdiction and edition; your local code and your equipment's manual control.